1ph or 3ph Voltage Monitoring relay

Installation: 8 Pin Socket

Model: DSP-DVR, DVR-M

 

Operation based on the direct line voltage detection

 

  • Protection: Over/Under voltage, Phase Loss, Reverse Phase, Current Unbalance

  • Indication : Voltage [Line/Average], Frequency

  • Time-Voltage operational characteristic → Define / Inverse

Rated Line Voltage → 100 ~ 500VAC

Over/Under Voltage protection within (+), (-) 20% to line voltage

Possible to preset operation time for over/under voltage each, respectively.


Perfect check for initial line state
a)"dt" (trip delay time) mode is preset "OFF"

 

  • Preset "a" in "out" mode:
    Main trip output(95-98) is energized (Open → Close) in case the rated line voltage with normal forward phase state is sensed initially

  • Main trip output(95-98) is trip as showing a trip cause if the initial line state is under over/under voltage, reverse phase, voltage unbalance

  • v.OFF is shown in case the line voltage is not sensed initially or voltage is dropped to zero(0) while the normal operation is doing

  • Preset "b" in "out" mode:
    Main trip output(95-98) is not energized (Open→ Open) in case the rated line voltage with normal forward phase state is sensed initially


b)"dt" (trip delay time) mode is preset a value(time)
 

  • Preset “a” in “out" mode: Main trip output(95-98) is energized (Open→ Close) after "dt" is elapsed in case the rated line voltage with normal forward phase state is sensed initially

  • Main trip output(95-98) is still opened(not trip) even after "at" is elapsed if the initial state is under phase loss, also "PL' is shown

  • "rp" is shown as main trip output(97-98) is still opened(not trip) after operational trip time(0.5sec) without concerning with "dt" if reverse state is sensed initially


Trip cause is shown by characters and/or numbers

  • 4 Digit Window/DVR Type

  • 5 Digit Window/DVR-M Type


3 phase line voltage/ average voltage and / or frequency is shown ordery every 3sec

Alarm history, latest 8 trip events

 

Reset after a trip: auto or manual

Self-diagnostics to check if this relay is ready to work or not